Cause & Consequence
- Uncontrolled release of a flammable gas or liquid
Incident Location
Fixed Installation
Incident Activity
Production operations
Specific Incident Equipment
Non Return Valve/Water wash tank
Lessons Identified
Gas had migrated back from the compressor casing into the water wash tank via two block valves, two non return valves and pump. One valve was partially open (a 1/3 of a turn off its seat) the other may have been “passing”. The 2 non return valves cannot be guaranteed to be tight shut off and may “pass”.
Incident Recommendations
Replace all NRV's and associated block valves in the compressor wash systems
Conduct a risk assessment to ensure the safe operation / running of both the compressor and compressor wash skid until the NRV’s and block valves are replaced.